PHASE: Single phase with ground
Capacity: 1000 VA / 800 W
INPUT
Voltage Range: - Low Line Transfer: 160 VAC/140 VAC/120 VAC/110 VAC ± 5% (Ambient Temp.<35°C)
Low Line Comeback: 175 VAC /155 VAC/ 135 VAC /125 VAC± 5 % (Ambient Temp.<35°C)
High Line Transfer: 300 VAC ± 5 %
High Line Comeback: 290 VAC ± 5 %
Frequency Range: 40Hz ~ 70 Hz
Power Factor: ≧ 0.99 @ nominal voltage
OUTPUT
Output Voltage: 208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode): ± 1%
Frequency Range (Synchronized Range): 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode): 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Current Crest Ratio: 3:1
Harmonic Distortion: ≦ 3 % THD (Linear Load), ≦ 6% THD (non-linear load)
Transfer Time: - AC Mode to Batt. Mode: Zero
Inverter to Bypass: 4 ms (Typical)
Waveform (Batt. Mode): Pure Sinewave
EFFICIENCY
AC Mode: 88%
Battery Mode: 83%
BATTERY
Battery Type: 12 V / 9 Ah
Numbers: 2
Typical Recharge Time: 4 hours recover to 90% capacity
Charging Current (max.): 1.0 A
Charging Voltage: 27.4 VDC ± 1%
INDICATORS
LCD Panel : UPS status, Load level, Battery level, Input / Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode: Sounding every 4 seconds
Low Battery: Sounding every second
Low Battery: Sounding twice every second
Fault: Continuously sounding
PHYSICAL
Dimension, D x W x H (mm): 282 x 145 x 220
Net Weight (kgs): 9.8
ENVIRONMENT
Humidity: 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level: Less than 50dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB: Supports Windows 2000/2003/XP/Vista/ 2008, Windows 7/8, Linux, Unix, and MAC
Optional SNMP: Power management from SNMP manager and web browser
NOTE 1: Derate to 80% of capacity in CVCF mode or when the output voltage is adjusted to 200/208VAC.
NOTE 2: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 10m.