True double-conversion design with high adaptability to harsh mains conditions. DSP design enables precise and reliable control. High efficiency results in energy saving. Supports energy-saving ECO mode. Compact size requiring small installation space. Built-in OVCD protection, fan lock detection, over temperature detection, overload warning to enhance the product reliability. USB HID enable monitoring on UPS without software installation. Intelligent communication slot enables remote monitoring. Programmable LCD display for quick UPS parameters configuration. Low audible noise at typical load.
Capacity: 3000 VA / 2700 W
Efficiency
Double coversion mode: 0.91
Eco Mode: Up to 98%
Input
Voltage range: 176-300V 100% load, 100-176V derating to 40% load linearly
Rated Frequency range: 50Hz-60Hz
Frequency range: 40Hz-70Hz(45Hz-55Hz 54Hz-66Hz @ load>60%)
Power factor: >0.99
THDI: <5%
Input connection: Wiring/socket IEC C19
Output
Rating Voltage: 220/230/240V
Rating Current: 45A
Frequency range Rated: 50Hz/60Hz
Frequency range: 40Hz-70Hz(45Hz-55Hz 54Hz-66Hz @ load>60%)
Maximum Power factor: 0.9
Voltage accuracy: ±1%
THDv: <2% linear load, <6% non-linear load
Transfer time: 0ms(4ms @ line , bypass;10ms @ ECO In- verter)
Crest Ratio: max 3:1
Overload (line mode): 100%
≤ 150% for 10 seconds. >150% for 0.3s.
Output connection Wiring/socket: 4 x IEC C13 + 1 x SA
Battery Voltage: 75VDC
Battery Capacity (AH): 6 x 12V/9Ah
Charger: Maximum charging current 1.5A
Other working mode: CVCF Yes (derating to 60% load)
HMI (human-machine interface)
Display: Segment LCD
USB: USB20.0
RS232: Yes
EPO: Yes
Intelligent slot: Yes
Network card: Yes, NMC mini card
Modbus card: Optional, CMC/Modbus Long Card
Dry contactor card: Optional, AS400 Long Card
Monitor software: Winpower
Dimension, D x W x H: 190mm x 393mm x 327mm
Net Weight: 22.7kg
IP protection level: IP20
Environmental and safety
EMC Standard: IEC/ EN 62040-2
Safety Standard: IEC/ EN 62040-1
Operation temperature: 0-40℃
Operating Altitude: 0~3000m(the load derating 1 % every up 100m@1000~3000m)
Acoustic Noise:
Store temperature: -25℃ to 55℃
Relative humidity: 0-95%
Installation procedure with free Software: 1. Go to the website: http://www.ups-software-download.com/content/ups-download-software/download.html 2. Choose the operation system you need and follow the instruction described on the website to download the software. When your computer restarts, the WinPower software will appear as a green plug icon located in the system tray, near the clock.